6 Parameter structure
6.4 Control signal terminals
130 DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com
6.4.2.4 P-12 = 4: Control via Modbus, ramps via Modbus
Table 36: P-12 = 4: Control via Modbus, ramps via Modbus
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0 START No function No function No function
1 Not permissible
2 Not permissible
3 START Select BUS REF/f-Fix1 EXTFLT No function
4 Not permissible
5 Not permissible
6 START Select BUS REF/AI1 REF EXTFLT AI1 REF
7
START Select BUS REF/DIG REF EXTFLT No function
8 Not permissible
9 Not permissible
10 Not permissible
11 Not permissible
12 Not permissible
13 START No function EXTFLT No function
14 Not permissible
15 START Select f-Fix/BUS REF Select Fire Mode/Normal OP Select f-Fix4/f-Fix2
16 START Select f-Fix4/BUS REF Select Fire Mode/Normal OP No function
17 START Select BUS REF/f-Fix4 Select Fire Mode/Normal OP No function