6 Parameter structure
6.6 Parameter
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 149
P-19 RO1 upper Limit 0.00 % 200.00 % Switching ON threshold of relay RO1
with P-18 = 4, …, 7, 10
100.00 %
P-20
Preset Speed 1 Min Frequency Max Frequency Preset Fixed Frequency 1
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
If P-09 is changed, the value is reset to default.
15.0 hz
P-21 Preset Speed 2 Min Frequency Max Frequency Preset Fixed Frequency 2
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
If P-09 is changed, the value is reset to default.
0.0 Hz
P-22
Preset Speed 3 Min Frequency Max Frequency Preset Fixed Frequency 3
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
If P-09 is changed, the value is reset to default.
0.0 Hz
P-23 Preset Speed 4 Min Frequency Max Frequency Preset Fixed Frequency 4
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
If P-09 is changed, the value is reset to default.
0.0 Hz
P-24
t-QuickDec 0.00 s 600.0 s Quick Stop Ramp
In default the second deceleration ramp is
activated by applying voltage to DI1 and DI2
(terminals 2 and 3) at the same time.
0.00 s
P-25
AO1 Function 0 12 Select Signal to show on the analog output
P-25 = 0, …, 7, 10, 11 = digital output
0: RUN, enable (FWD/REV)
1: READY, DC1...E1 ready for operation
2: Speed = speed reference value
3: Fault (DC1...E1 not ready)
4: Speed RO1 Upper Limit (P-19)
5: Motor current RO1 Upper Limit (P-19)
6: Speed < RO1 Upper Limit (P-19)
7: Motor current < RO1 Upper Limit (P-19)
10: Drive not enabled
11: Speed not at reference value
P-25 = 8, 9, 12 = analog output
8: Output Frequency (0 - 100 % f-max (P-01))
9: Motor current (0 - 200 % Motor Nom Current
(P-08))
12: Motor power
8
P-26 f-SkipBand1 0.0 Hz Max Frequency Skip frequency band width
Defines the frequency range around f-Skip1 in
which the drive doesn’t work in steady-state to
avoid mechanical resonances in the application.
During acceleration and deceleration this range is
passed through by using the ramps set with P-03
and P-04.
0.0 Hz
Para-
meter
Designation min. value max. value Description DS