7 Technical Data
7.1 General rated operational data
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 159
Motor feeder
Output voltage U
2
V 1~ 0 - U
e
Assigned motor output
at 115 V, 50 Hz P kW 0.37 - 0.55
at 230 V, 50 Hz P kW 0.37 - 1.1
Output Frequency
Range, parameterizable f
2
Hz 0 - 50/60 (max. 500 Hz)
resolution Hz 0.1
Rated operation current I
e
A 4.3 - 11
Overload current for 60 s every 600 s i
l
% 150
Overload current for 3.75 s every 600 s i
l
% 175
Switching frequency (double modulation) f
PWM
kHz max. 32
Operating mode
V/Hz control (speed accuracy) ±20 %, with slip compensation
Response time (enable IGBT) t
r
ms < 10
Brake chopper only for size FS2
Braking current during continuous operation % 100 (I
e
)
Maximum braking current % 150 for 60 s
Technical data Symbol Unit Value