EasyManua.ls Logo

Eaton PowerXL - Voltage Categories

Eaton PowerXL
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Device series DC1-S…
1.6 Voltage categories
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives 05/21 MN040058EN www.eaton.com 19
1.6 Voltage categories
DC1-S… variable frequency drives are divided into two voltage categories:
115 V: 110 - 115 V ±10 %
DC1-S1
200 V: 200 - 240 V ±10 %
DC1-S2
DC1-S1
Single-phase mains connection, rated operating voltage 115 V
U
LN
= 1~, 110 - 115 V ±10 %, 50/60 Hz
I
e
= 7 - 11 A
Motor: 0.37 - 0.55 kW (115 V, 50 Hz), 1/2 - 3/4 HP (115 V, 60 Hz)
DC1-S2
Single-phase mains connection, rated operating voltage 230 V
U
LN
= 1~, 200 - 240 V ±10 %, 50/60 Hz
I
e
= 4.3 - 11 A
Motor: 0.37 - 1.1 kW (230 V, 50 Hz), 1/2 - 1.5 HP (230 V, 60 Hz)
Figure 8: DC1-S1… / DC1-S2…
Mains, U
LN
= 1 ~ 110 - 115 V ±10 %
U
LN
= 1 ~ 200 - 240 V ±10 %
115 V (U
LN
= 115 V)
230 V (U
LN
= 230 V)
L
N
PE
U
V
U1
V1
EMC Filter
L1/L
L2/N
BRDC+
M
1∼
Motor
I
e
Brake chopper
(DC1-S…B-A20…)
FS2