Eaton Corporation Page 29 Ver 1.1
E. AC Protection
I) If an external AC breaker or fuse protector is installed, it is not
necessary to implement AC protection fuses within the wiring box. The
specification of external breakers or fuses shall meet the recommended
ratings listed in the following table.
II) If there is no external AC breaker or fuse protector installed, it is
recommended to have AC protection fuses installed to the AC side. And
the AC fuse that can be selected from the recommended list as below
table indicates.
To ensure the rating of the fuses that are used for the each model is
correct, it is strongly recommended the installer purchase the AC fuses
that have already been tested by Eaton.
The recommended list for the AC Fuses:
Model Manufacturer
Part Numbers Fuses Rating
PV240 (PV238)
Littelfuse KLC 25
25A / 600V
AC
PV250 Littelfuse KLC 30
30A / 600V
AC
PV260 Littelfuse L50S 40
40A / 500V
AC
PV270 Littelfuse L50S 50
50A / 500V
AC