10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
112 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
– 20D7 Active energy (reverse) Wh 1
– 20D8 Active energy combined (= forward + reverse) Wh 1
– 20D9 Apparent energy VAh 1
2054 20DA Peak reactive power demand Var 1
2055 20DB Peak apparent power demand VA 1
205A 20E0 Active power demand W 1
205B
20E1 Reactive power demand Var 1
205C 20E2 Apparent power demand VA 1
205D
20E3 Minimum value - I
L1
(IA) A 10
205E
20E4 Maximum value - I
L1
(IA) A 10
205F 20E5 Minimum value - I
L2
(IB) A 10
2060 20E6 Maximum value - I
L2
(IB) A 10
2061 20E7 Minimum value - I
L3
(IC) A 10
2062 20E8 Maximum value - I
L3
(IC) A 10
2063 20E9 Minimum value - I
G
(IG) A 10
2064 20EA Maximum value - I
G
(IG) A 10
2065 20EB Minimum value - I
N
(IN) A 10
2066 20EC Maximum value - I
N
(IN) A 10
2067
20ED Minimum value - U
L1
(VA) V 10
2068 20EE Maximum value - U
L1
(VA) V 10
2069 20EF Minimum value - U
L2
(VB) V 10
206A 20F0 Maximum value - U
L2
(VB) V 10
206B 20F1 Minimum value - U
L3
(VC) V 10
206C 20F2 Maximum value - U
L3
(VC) V 10
206D
20F3 Minimum value - U
L1-N
(VAN) V 10
206E
20F4 Maximum value - U
L1-N
(VAN) V 10
206F 20F5 Minimum value - U
L2-N
(VAN) V 10
2070 20F6 Maximum value - U
L2-N
(VAN) V 10
2071
20F7 Minimum value - U
L3-N
(VAN) V 10
2072
20F8 Maximum value - U
L3-N
(VAN) V 10
2073 20F9 Overload pre-warning % 1
2081
2107 Counter - I
sd
, I
i
tripping – 1
2082 2108 Counter - I
r
, I
g
tripping – 1
2083
2109 Operations counter – 1
2084
210A Counter - I
sd
tripping – 1
2085 210B Counter - I
i
tripping – 1
2086 210C Counter - bypass tripping – 1
Index (Hex)
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit Scale
factor (FP)