10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 113
2087 210D Counter - I
r
tripping – 1
2088 210E Counter - I
g
tripping – 1
2089 210F Counter - trips total – 1
208A 2110 Counter - test mode tripping – 1
208B 2111 Counter - number of openings via the communica-
tion interface
– 1
208C
2112 Counter - external actuation
1)
– 1
208D
2113 Time of last actuation
(year, month, day, hour, minute, second)
– –
208E
2114 Operating time
2)
in minutes min 1
208F 2115 Operating time
2)
in hours h 1
2090 2116 Operating time
2)
in days d 1
2091
2117 Residual life
3)
points –
1) An external actuation is a switching operation that is not initiated by the trip unit, such as manual switching,
switching via an externally wired remote operator or the actuation of a push-to-trip button.
2) The operating time counter will start as soon as the device is energized, either autonomously or through an
external power supply.
3) 0 points ≙ 100 % residual life
10.000 points ≙ 0 % residual life
Conversion formula: Residual life expressed as a percentage = 100 - (point value / 100)
Index (Hex)
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit Scale
factor (FP)