10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
124 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
Table 68: Setting group 2: “Modbus” group - EtherCAT
Index
[Hex]
Bit
field
Mask
field
Setpoint name R/W Format Description or value Unit
2002 15 - 0 0xFFFFFF Password W Encoded 0000 (default setting)
2003 15 - 0 0xFFFFFF Group 2 = on-
board Modbus
R/W Encoded 0x02FF
2004
15 - 0 Integrated
Modbus - commu-
nication address
R/W Encoded 001 - 247 (default setting 002)
2005 15 - 0 Integrated
Modbus - baud
rate
R/W Encoded 00: 9,600 bit/s
01: 19,200 bit/s (default setting)
02: 38,400 bit/s
02: 57,600 bit/s
2006
15 - 0 Integrated
Modbus - parity
R/W Encoded 00: none
01: odd
02: even (default setting)
2007
15 - 0 Integrated
Modbus - stop bit
R/W Encoded 00: 1 bit
01: 2 bits (default setting)