10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
152 PXR Electronic trip unit 01/21 MN012005EN www.eaton.com
The following indexes are assigned to the data objects.
Table 89: Event summary - Profinet
Table 90: Historical trip / major alarm event - Profinet
Index [Hex]
Format R/W Description (historical event overview)
13C Encoded R/W Event type: summary = 0x8EFF
13D Unsigned 32 R Earliest event ID
13E Unsigned 32 R Latest event ID
13F Unsigned 32 R/W Requested event ID
140 Unsigned 32 R Previous event ID
141 Unsigned 32 R Next event ID
142 Date/time R Date/time
143
Encoded R Data format
0x0000, 0x0001, 0x0004, 0x0005, 0x0005, 0x0006
144
B0 R Valid bit of the object
145 Encoded R Cause of event:
00: boot process - time OK
01: download of the setpoint values
02: time has been adjusted
03: trip
04: alarm
05: test mode has been selected
06: exiting the test mode
08: boot process - no time
09: test completed
10: maintenance mode activated
11: maintenance mode deactivated
12: opened via the communication interface
13: closed via the communication interface
Index [Hex]
Format R/W Description
(historical event overview)
Unit
13C Encoded R/W Event type:
Trip: 0x80FF
Alarm: 0x81FF
13D Unsigned 32 R Earliest event ID
13E Unsigned 32 R Latest event ID
13F Unsigned 32 R/W Requested event ID
140 Unsigned 32 R Previous event ID
141 Unsigned 32 R Next event ID
142 Date/time R Date/time
143 Encoded R Data format:
Trip: 0x0004
Main alarm: 0x0005
144
Bit 15 - Bit 0 R Valid bits of the object
145
Bit 31 - Bit 16 R Valid bits of the object
146 Encoded R Status reason
(primary, secondary, reason)

Table of Contents