10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.3 Profinet
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 153
Table 91: Minor alarm event - Profinet
147
Unsigned 32 R I
L1
(IA) A
148 Unsigned 32 R I
L2
(IB) A
149 Unsigned 32 R I
L3
(IC) A
14A Unsigned 32 R I
N
(IN) A
14C Unsigned 32 R I
G
(IG residual) A
14D Unsigned 16 R U
L1-L2
(VAB) V
14E Unsigned 16 R U
L2-L3
(VBC) V
14F Unsigned 16 R U
L3-L1
(VCA) V
150 Unsigned 16 R U
L1-N
(VAN) V
151 Unsigned 16 R U
L2-N
(VBN) V
152
Unsigned 16 R U
L3-N
(VCN) V
153
Signed 32 R Active 3-phase power W
154 Signed 32 R Reactive 3-phase power VAR
155 Unsigned 32 R Apparent 3-phase power VA
156 Signed 32 R Active power demand W
157 Signed 32 R Reactive power demand VAR
158 Unsigned 32 R Apparent power demand VA
15A Unsigned 32 R Frequency 1/10 Hz
15C Unsigned 32 R Number of operations –
15D Bit 31 - Bit 0 R Binary status with valid bits –
Index [Hex] Format R/W Description
(historical event overview)
13C Encoded R/W Event type:
Summary = 0x81FF
13D
Signed 32 R Earliest event ID
13E
Signed 32 R Latest event ID
13F Signed 32 R/W Requested event ID
140 Signed 32 R Previous event ID
141
Signed 32 R Next event ID
142
Date/time R Date/time
143 Encoded R Data format:
Small alarm: 0x0006
144
Bit 0 R Valid bits of the object
145
Encoded R Status reason
(primary, secondary, reason code)
Index [Hex] Format R/W Description
(historical event overview)
Unit