Communications
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
DCTools Communications Setup
► To connect to the SC200 with DCTools:
1 If not already installed, install the PC modem (hardware and software) according to the
manufacturer's instructions.
2 Install DCTools on the PC/laptop.
3 Double-click the DCTools icon to open the Connection Manager window.
4 Go to Connection > New to open a new connection dialog box.
5 Enter:
Select the COM port used by the modem (if external) or the
modem name.
0 (0 = Broadcast, 1-65279 = individual address)
The number of the PSTN line used by the modem.
Clear if a logon script is not required for the modem.
Select if a logon script is required. Click Logon Script to define.
For more details, see DCTools online help (press F1).
6 Press OK. DCTools will now connect to the SC200.
7 See System Operation on page 21 for details of the SC200 control and monitoring functions
available via DCTools.
For help using DCTools press F1.
8 If required, access to the SC200 via DCTools can be password controlled. See Write Access
Password on page 95.
SMS Text Messaging Setup (if required)
For additional information see Application Note AN0112. To receive application notes see
Worldwide Support on page 125.
► To enable SMS alarm messages
1 Connect to the SC200 with DCTools/Web.
2 Go to Configuration > Communications > Serial.
3 Click on
to expand SMS Notifications.
4 For each cellphone to receive SMS alarm messages set the Phone Number and other details
as required.
5 Type the required Prefix string if alarm messages are to be sent to an email address.
This requires a GSM-Email Gateway connected to the GSM network. Contact the GSM
network operator for details of the Prefix string required at the beginning of the SMS message.
Emails can also be sent via an IP network. See details on page 87.