SC200 Handbook
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
185 (or a different value if required)
5 (or a different value if required)
Batteries
The following information is available about the batteries connected to the dc power system.
Charge - the battery current is above
the Battery State Threshold.
Discharge - the battery current is below
-1 * Battery State Threshold.
Floating - the battery current is between
± Battery State Threshold.
Unavailable - the battery current is not
available.
See SC200 or DCTools/Web displays
??? or N/A on page 101.
SC200: Battery > Battery
DCTools/Web: Batteries
The temperature measured by the battery
temperature sensor.
The current level of battery discharge.
See also Reset Battery State on page 63.
Batteries Configuration
The following battery parameters must be configured.
The number of 2V cells per battery string (for
example: 24 in a 48V nominal system).
SC200: Battery > Battery
(tab)
DCTools/Web: Batteries
Set to the rated 10 hour capacity of the installed
battery strings.
Used to determine the Battery Charge State. See
Battery Charge State on page 56.
An optional text field for the name or type of
battery.
Battery Current
Sensor Fail
Recognition Period
An optional battery current sensor fail delay.
Set if momentary battery current sensor fail
conditions stop battery related control processes.