SC200 Handbook
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
► To manually control a digital output
Either:
In DCTools/Web go to Digital Outputs:
Expand the Digital Outputs table.
In the Control State column of the required digital output, select Active or Inactive.
Or, use the SC200 keypad to go to Digital Outputs:
Select the required digital output. Press Edit.
Select Active or Inactive. Press Save.
The DO Manual alarm (if enabled) will activate.
The corresponding digital output will Energize or De-Energize, as selected in the Active
State column of the Digital Outputs table.
While Active or Inactive is selected, the DO will not be operated by any active alarms mapped
to it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.
► To set the state of a digital output from PowerManagerII
In DCTools, set the Group of one or more digital outputs to a non-zero value.
Only digital outputs with a non-zero Group are visible in PowerManagerII
In PowerManagerII select the SiteManager group item.
Click on the Realtime tab.
From the drop down list beside the digital output select Active Manual or Inactive Manual.
The DO Manual alarm (if enabled) will activate.
The corresponding digital output will Energize or De-Energize, according to its Active State.
While Active Manual or Inactive Manual is selected, the DO will not be operated by any active
alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the
digital output.
► To configure a digital output
1 In DCTools/Web go to Digital Outputs. Expand the Digital Outputs table.
2 Select a Digital Output (1-6*).
Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules
are connected. See details in the dc power system Installation and Operation Guide.
3 Configure the following parameters to suit the application.
To change a setting, double-click and select from drop down list or edit the text.