The following information is available about Battery Time Remaining.
Parameter Description Where to find:
Time Remaining During a battery discharge, this is the estimated
time until the battery voltage will be equal to the
End Voltage, at the present battery current. Time
remaining will be re-calculated if the load
current varies during discharge (for example,
when a load disconnect LVD operates).
Time Remaining is only available when Battery
Time Remaining State is Active.
SC300: Battery
Web/DCTools: Batteries
Battery State Of
Health
The approximate battery capacity measured
during the last battery characterization, as a
percentage of the configured Battery Capacity.
Web/DCTools: Batteries
State Inoperative: The battery characterization data is
not loaded, End Voltage is below the
characterization end point, or the bus voltage or
battery current is unavailable.
Inactive: Battery Charge State is Float or Charge.
See Battery Charge State on page 68.
Characterizing: Battery characterization is in
progress.
Active: The battery has been characterized and
Battery Charge State is Discharge.
See Battery Charge State on page 68.
SC300: Battery
Web/DCTools: Batteries >
Battery Time Remaining
Lowest End
Voltage
The end voltage used for the last battery
characterization.
Characterization
Result
Not Yet Run: The battery has not been
characterized since the last restart of the SC300.
Active: The SC300 is collecting the
characterization data.
Complete: The SC300 has collected the
characterization data and is updating its
database.
Updated: The SC300 has updated its database.
Sensor Failed: Data from the last
characterization was not saved because the bus
voltage sensor failed or the battery current
became unavailable.
Not Fully Charged: Characterization did not
start because the battery was not fully charged
when discharge started.
Unstable Battery Current Pending: The battery
current has varied more than the tolerance for an
accurate characterization. Characterization will
continue if the battery current is in tolerance
within two minutes. Otherwise, data from this
discharge will not be saved.
Unstable Battery Current: Data from the last
characterization was not saved because the
battery current varied more than the tolerance,
for more than two minutes.
Voltage Step Detected: Data from the last