SLX9000 Adjustable Frequency Drives User Manual
8-8 For more information visit: www.eaton.com
MN04003020E
January 2009
Table 8-5: Basic Parameters P2.1, continued
Code Parameter Min. Max. Unit Default Cust ID Note
P2.1.16 Analog output
function
0 12 1 307 0 = Not used
1 = Output freq. (0 – f
max
)
2 = Freq. reference (0 – f
max
)
3 = Motor speed (0 – Motor nominal
speed)
4 = Output current (0 – I
nMotor
)
5 = Motor torque (0 – T
nMotor
)
6 = Motor power (0 – P
nMotor
)
7 = Mot. voltage (0 – V
nMotor
)
8 = DC-link volt (0 – 1000V)
9 = PI controller ref. value
10 = PI contr. act. value 1
11 = PI contr. error value
12 = PI controller output
P2.1.17
DIN2 function 0 10 1 319 0 = Not used
1 = Start Reverse (DIN1 = Start
forward)
2 = Reverse (DIN1 = Start)
3 = Stop pulse (DIN1 = Start pulse)
4 = External fault, cc
5 = External fault, oc
6 = Run enable
7 = Preset speed 2
8 = Motor pot. UP (cc)
9 = Disable PID (Direct freq.
reference)
10 = Interlock 1
P2.1.18
DIN3 function 0 17 6 301 0 = Not used
1 = Reverse
2 = External fault, cc
3 = External fault, oc
4 = Fault reset
5 = Run enable
6 = Preset speed 1
7 = Preset speed 2
8 = DC-braking command
9 = Motor pot. UP (cc)
10 = Motor pot. DOWN (cc)
11 = Disable PID (Direct freq.
reference)
12 = PID Keypad ref. 2 selection
13 = Interlock 2
14 = Thermistor input
Note! See Page 4-9
15 = Force control place to I/O
16 = Force control place to Fieldbus
17 = AI1/AI2 selection for I/O
reference