SLX9000 Adjustable Frequency Drives User Manual
8-10 For more information visit: www.eaton.com
MN04003020E
January 2009
Table 8-6: Input Signals, P2.2, continued
Code Parameter Min. Max. Unit Default Cust ID Note
P2.2.7 AI1 custom
minimum setting
0.00 100.00 % 0.00 380
P2.2.8 AI1 custom
maximum setting
0.00 100.00 % 100.00 381
P2.2.9 AI1 inversion 0 1 0 387 0 = Not inverted
1 = Inverted
P2.2.10 AI1 filter time 0.00 10.00 s 0.10 378 0 = No filtering
P2.2.11 AI2 signal selection 0 11 388 Same as parameter 2.2.5
P2.2.12 AI2 signal range 1 4 2 390 Not used if AI2 Custom min <> 0% or
AI2 custom max. <> 100%
1 = 0 – 20 mA
2 = 4 – 20 mA
3 = 0V – 10V
4 = 2V – 10V
P2.2.13 AI2 custom
minimum setting
0.00 100.00 % 0.00 391
P2.2.14 AI2 custom
maximum setting
0.00 100.00 % 100.00 392
P2.2.15 AI2 inversion 0 1 0 398 0 = Not inverted
1 = Inverted
P2.2.16 AI2 filter time 0.00 10.00 s 0.10 389 0 = No filtering
P2.2.17 Motor
potentiometer
frequency reference
memory reset
0 2 1 367 0 = No reset
1 = Reset if stopped or powered
down
2 = Reset if powered down
P2.2.18 Reference scaling
minimum value
0.00 P2.2.19 0.00 344 Does not affect the fieldbus reference
(Scaled between par. 2.1.1 and par.
2.1.2
)
P2.2.19 Reference scaling
maximum value
P2.2.18 320.00 0.00 345 Does not affect the fieldbus reference
(Scaled between par. 2.1.1 and par.
2.1.2
)
P2.2.20 Keypad control
reference selection
0 5 2 121 0 = AI1
1 = AI2
2 = Keypad reference
3 = Fieldbus reference
(FBSpeedreference)
4 = Motor potentiometer
5 = PID controller
P2.2.21 Fieldbus control
reference selection
0 5 3 122 See above