SLX9000 Adjustable Frequency Drives User Manual
8-12 For more information visit: www.eaton.com
MN04003020E
January 2009
Table 8-7: Output Signals, G2.3, continued
Drive Control Parameters (Control Keypad: Menu P2 ➔ P2.4)
Table 8-8: Drive Control Parameters, P2.4
Prohibit Frequency Parameters (Control Keypad: Menu P2 ➔ P2.5)
Table 8-9: Prohibit Frequency Parameters, P2.5
Code Parameter Min. Max. Unit Default Cust ID Note
P2.3.14 Analog input
supervision
0 2 0 356 0 = Not used
1 = AI1
2 = AI2
P2.3.15 AI supervision
OFF limit
0.00 100.00 % 10.00 357
P2.3.16 AI supervision ON
limit
0.00 100.00 % 90.00 358
P2.3.17 Relay output 1 ON
delay
0.00 320.00 s 0.00 487 ON delay for RO1
P2.3.18 Relay output 1
OFF delay
0.00 320.00 s 0.00 488 OFF delay for RO1
Code Parameter Min. Max. Unit Default Cust ID Note
P2.4.1 Ramp 1 shape 0.0 10.0 s 0.0 500 0 = Linear
>0 = S-curve ramp time
P2.4.2
Brake chopper 0 3 0 504 0 = Disabled
1 = Used in Run state
3 = Used in Run and Stop state
P2.4.3 DC braking
current
0.15 x I
n
1.5 x I
n
A Varies 507
P2.4.4 DC braking time
at stop
0.00 600.00 s 0.00 508 0 = DC brake is off at stop
P2.4.5 Frequency to start
DC braking during
ramp stop
0.10 10.00 Hz 1.50 515
P2.4.6 DC braking time
at start
0.00 600.00 s 0.00 516 0 = DC brake is off at start
P2.4.7 Flux brake 0 1 0 520 0 = Off
1 = On
P2.4.8 Flux braking
current
0.0 Varies A 0.0 519
Code Parameter Min. Max. Unit Default Cust ID Note
P2.5.1 Prohibit frequency
range 1 low limit
0.0 Par.
2.5.2
Hz 0.0 509 0 = Not used
P2.5.2 Prohibit frequency
range 1 high limit
0.0 Par.
2.1.2
Hz 0.0 510 0 = Not used
P2.5.3 Prohibit
frequencies acc./
dec. ramp scaling
0.1 10.0 times 1.0 518 Multiplier of the currently selected
ramp time between prohibit
frequency limits