SLX9000 Adjustable Frequency Drives User Manual
9-16 For more information visit: www.eaton.com
MN04003020E
January 2009
Figure 9-9: Relay Output 1 ON- and OFF-Delays
Drive Control
Figure 9-10: Acceleration/Deceleration (S-Shaped)
2.3.17 Relay output 1 ON delay ID487
2.3.18 Relay output 1 OFF delay ID488
With these parameters you can set on- and off-delays to relay output 1 (par 2.3.1).
RO1 Output
Signal Programmed
to Relay Output
ON-Delay
ID487
OFF-Delay
ID488
2.4.1 Acceleration/Deceleration ramp 1 shape ID500
The start and end of the acceleration and deceleration ramps can be smoothed with
this parameter. Setting value 0 gives a linear ramp shape which causes acceleration
and deceleration to act immediately to the changes in the reference signal.
Setting value 0.1 – 10 seconds for this parameter produces an S-shaped acceleration/
deceleration. The acceleration time is determined with parameters 2.1.3/2.1.4.
ID500 (2.4.1)
ID500 (2.4.1)
ID103, ID104
(2.1.3, 2.1.4)
t
Hz

Table of Contents