SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 9-31
January 2009
Auto Restart Parameters
The automatic restart function is active if the value of par. 2.1.21 = 1. There are always three
restart trials.
2.7.19 Response to thermistor fault ID732
0 No response
1 Warning
2 Fault, stop mode after fault according to parameter 2.1.12
3 Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection.
2.7.20 Response to fieldbus fault ID733
Sets the response mode for the fieldbus fault if a fieldbus board is used. For more
information, see the respective Fieldbus Board Manual.
See parameter 2.7.19.
2.7.21 Response to slot fault ID734
Sets the response mode for a board slot fault due to missing or broken board.
See parameter 2.7.19.
2.7.22 Actual value supervision function ID735
0 Not used
1 Warning, if actual value falls below the limit set with par. 2.7.23
2 Warning, if actual value exceeds the limit set with par. 2.7.23
3 Fault, if actual value falls below the limit set with par. 2.7.23
4 Fault, if actual value exceeds the limit set with par. 2.7.23
2.7.23 Actual value supervision limit ID736
With this parameter you can set the limit of actual value supervised by par. 2.7.22.
2.7.24 Actual value supervision delay ID737
Sets the delay for the actual value supervision function (par. 2.7.22).
If this parameter is in use, the function of par. 2.7.22 will be active only when the
actual value stays outside the defined limit for the time determined by this
parameter.
2.8.1 Automatic restart: Wait time ID717
Defines the time before the drive tries to automatically restart the motor after the
fault has disappeared.