2.8.2 Automatic restart: Trial time ID718
The Automatic restart function restarts the drive when the faults have disappeared
and the waiting time has elapsed.
The time count starts from the first autorestart. If the number of faults occurring
during the trial time exceeds three, the fault state becomes active. Otherwise the
fault is cleared after the trial time has elapsed and the next fault starts the trial time
count again.
If a single fault remains during the trial time, a fault state is true.
2.8.3 Automatic restart, start function ID719
The Start function for Automatic restart is selected with this parameter. The
parameter defines the start mode:
0 Start with ramp
1 Flying start
2 Start according to par. 2.1.11
Fault Trigger
Motor Stop Signal
Motor Start Signal
Supervision
Fault State Active
RESET/Fault Reset
Wait Time
Par. ID717
Wait Time
Par. ID717
Wait Time
Par. ID717
Restart 1 Restart 2
Trial Time
Par. ID718
Auto Function: (Trials = 2)