SLX9000 Adjustable Frequency Drives User Manual
3-2 For more information visit: www.eaton.com
MN04003020E
January 2009
Figure 3-3: FR8 Power and Motor Wiring Terminals
Use cables with heat resistance of at least +70°C. The cables and the fuses must be
dimensioned according to Tables 3-1 and 3-2. Installation of cables according to UL
regulations is found on Page 3-15.
The fuses also function as cable overload protection.
These instructions apply only to cases with one motor and one cable connection from the
drive to the motor. In any other case, ask the factory for more information.