SLX9000 Adjustable Frequency Drives User Manual
3-4 For more information visit: www.eaton.com
MN04003020E
January 2009
Table 3-3: Cable and Fuse Sizes – 480V Ratings
UL recognized type RK.
Based on a maximum environment of 104°F (40°C).
Table 3-4: Cable and Fuse Sizes – 575V Ratings
UL recognized type RK.
Based on a maximum environment of 104°F (40°C).
hp
Frame
Size I
l
(A)
Fuse
(A)
Wire Size
Terminal Size
Power Ground Power Ground
1-1/2
2
3
5
MF4 3.3
4.3
5.6
7.6
10
10
10
10
14
14
14
14
14
14
14
14
12 – 16
12 – 16
12 – 16
12 – 16
14 – 16
14 – 16
14 – 16
14 – 16
7-1/2
10
15
MF5 12
16
23
15
20
30
12
10
8
12
10
8
8 – 16
8 – 16
8 – 16
8 – 16
8 – 16
8 – 16
20
25
30
MF6 31
38
46
35
50
60
8
6
4
8
8
6
1/0 – 14
1/0 – 14
1/0 – 14
2 – 10
2 – 10
2 – 10
40
50
60
FR7 61
72
87
80
100
110
2
2
1/0
6
6
4
1/0 – 14
1/0 – 14
1/0 – 14
2/0 – 10
2/0 – 10
2/0 – 10
75 FR8 105 125 2/0 2 4 – 3/0 3/0 – 4
hp
Frame
Size I
l
(A)
Fuse
(A)
Wire Size
Terminal Size
Power Ground Power Ground
2
3
5
7-1/2
MF6 3.3
4.5
7.5
10
10
10
10
15
14
14
14
12
14
14
14
14
14 – 1/0
14 – 1/0
14 – 1/0
14 – 1/0
14 – 2
14 – 2
14 – 2
14 – 2
10
15
20
25
13.5
18
22
27
20
30
35
40
10
10
8
8
12
10
8
8
14 – 1/0
14 – 1/0
14 – 1/0
14 – 1/0
14 – 2
14 – 2
14 – 2
14 – 2
30
40
FR7 34
41
50
60
6
4
8
6
14 – 1/0
14 – 1/0
10 – 1/0
10 – 1/0
50
60
75
FR8 52
62
80
80
100
125
2
1
1/0
6
6
6
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0
4 – 3/0