SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 4-7
January 2009
Table 4-6: Option Board A2 Terminal Descriptions, All 230V, FR7 – FR8 460V and All 575V
Jumper Selections on SLX9000 Basic Board
The user is able to customize the functions of the drive to better suit an application by
selecting certain positions for the jumpers on the SLX9000 board. The positions of the
jumpers determine the signal type of analog input (terminal #2) and whether the termination
resistor RS-485 is used or not.
The following figures present the jumper selections of SLX9000 drives:
Figure 4-4: Jumper Selection for SLX9000, MF4 – MF6
Terminal Signal Technical Information
21 RO1/1 Normally Closed (NC) Switching Capacity:
24V DC / 8A
250V AC / 8A
125V DC / 0.4A
Min Switching Load: 5V/10 mA
Continuous Capacity: <2 Arms
22 RO1/2 Common
23 RO1/3 Normally Open (NO)
24 RO2/1 Normally Closed (NC) Switching Capacity:
24V DC / 8A
250V AC / 8A
125V DC / 0.4A
Min Switching Load: 5V/10 mA
Continuous Capacity: <2 Arms
25 RO2/2 Common
26 RO2/3 Normally Open (NO)
Jumper Block X8:
AI1 Mode
AI1 Mode: 0...20 mA; Current Input
AI1 Mode: Voltage Input; 0...10V
Jumper Block X13:
AI2 Mode
AI2 Mode: 0...20 mA; Current Input
AI2 Mode: Voltage Input; 0...10V
AI2 Mode: Voltage Input; 0...10V (Differential)
Jumper Block X9:
Ter m ination Resistor RS-485 Is in Use
Ter m ination Resistor RS-485 Is Not Used
= Factory Default