SLX9000 Adjustable Frequency Drives User Manual
MN04003020E
For more information visit: www.eaton.com 5-13
January 2009
System Menu (S6)
You can enter the System Menu from the Main menu by pressing Menu Button Right when
the location indication S6 is visible on the first line of the keypad display.
The controls associated with the general use of the drive, such as keypad settings,
customized parameter sets or information about the hardware and software are located
under the System Menu.
Table 5-8 has a list of the functions available in the System Menu.
Table 5-8: System Menu Functions
Code Function Min. Max. Unit Default Cust. Selections
S6.3 Copy parameters
P6.3.1 Parameter sets 0 = Select
1 = Store set 1
2 = Load set 1
3 = Store set 2
4 = Load set 2
5 = Load factory defaults
6 = Fault
7 = Wait
8 = OK
S6.5 Security
P6.5.2 Parameter lock 0 1 0 0 = Change Enabled
1 = Change Disabled
S6.6 Keypad settings
P6.6.1 Default page 0 1.1
P6.6.3 Timeout time 5 65535 s 1200
S6.7 Hardware settings
P6.7.2 Fan control 0 0 0 = Continuous
1 = Temperature (only sizes
MF4 and larger)
P6.7.3 HMI acknowledg.
timeout
200 5000 mS 200
P6.7.4 HMI number of
retries
110 5
S6.8 System info
S6.8.1 Counters menu
C6.8.1.1 Mwh counter KWh
C6.8.1.2 Operating days
counter
hh:mm:
ss
C6.8.1.3 Operating hours
counter
hh:mm:
ss
S6.8.2 Trip counters
T6.8.2.1 MWh trip counter kWh
P6.8.2.2 Clear MWh trip
counter
0 = No action
1 = Clear MWh trip counter
T6.8.2.3 Operating days trip
counter