Table 5-16: Output Process Data
Table 5-17: Input Process Data
Table 5-18: Status Word
Information about the status of the device and messages is indicated in the Status word. The
Status word is composed of 16 bits the meanings of which are described in Table 5-19.
Table 5-19: Actual Speed
This is actual speed of the drive. The scaling is -10000 – 10000. In the application, the value is
scaled in percentage of the frequency area between set minimum and maximum frequency.
Addr. Modbus Register Name Scale Type
2101 32101, 42101 FB Status Word Binary coded
2102 32102, 42102 FB General Status Word Binary coded
2103 32103, 42103 FB Actual Speed 0.01 %
2104 32104, 42104 Motor speed 0.01 +/- Hz
2105 32105, 42105 Motor speed 1 +/- Rpm
2106 32106, 42106 Motor current 0.1 A
2107 32107, 42107 Motor Torque 0.1 +/- % (of nominal)
2108 32108, 42108 Motor Power 0.1 +/- % (of nominal)
2109 32109, 42109 Motor Voltage 0.1 V
2110 32110, 42110 DC Voltage 1 V
2111 32111, 42111 Active Fault Fault code
Addr. Modbus Register Name Scale Type
2001 32001, 42001 FB Control Word Binary coded
2002 32002, 42002 FB General Control Word Binary coded
2003 32003, 42003 FB Speed Reference 0.01 %
2004 32004, 42004 PID Control Reference 0.01 %
2005 32005, 42005 PID Actual Value 0.01 %
2006 32006, 42006
2007 32007, 42007
2008 32008, 42008
2009 32009, 42009
2010 32010, 42010
2011 32011, 42011
15141312111098765 43210
————————F Z AREF W FLT DIR RUN RDY
15141312111098765 43210
MSB—————————— ———LSB