EasyManua.ls Logo

Eaton SLX9000 - Monitoring Values (Control Keypad: Menu M1); Table 7-1: Monitoring Values

Eaton SLX9000
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SLX9000 Adjustable Frequency Drives User Manual
7-2 For more information visit: www.eaton.com
MN04003020E
January 2009
Monitoring Values (Control Keypad: Menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses
and measurements. Monitoring values cannot be edited. See Page 5-7 for more information.
Table 7-1: Monitoring Values
Code Parameter Unit ID Description
V1.1 Output frequency Hz 1 Frequency to the motor
V1.2 Frequency reference Hz 25
V1.3 Motor speed rpm 2 Calculated motor speed
V1.4 Motor current A 3 Measured motor current
V1.5 Motor torque % 4 Calculated actual torque/nominal torque
of the unit
V1.6 Motor power % 5 Calculated actual power/nominal power
of the unit
V1.7 Motor voltage V 6 Calculated motor voltage
V1.8 DC-link voltage V 7 Measured DC-link voltage
V1.9 Unit temperature °C 8 Heatsink temperature
V1.10 Analog input 1 V 13 AI1
V1.11 Analog input 2 14 AI2
V1.12 Analog output current 26 AO1
V1.13 Analog output current 1, expander board mA 31
V1.14 Analog output current 2, expander board mA 32
V1.15 DIN1, DIN2, DIN3 15 Digital input statuses
V1.16 DIE1, DIE2, DIE3 33 I/O expander board: Digital input statuses
V1.17 RO1 34 Relay output 1 status
V1.18 ROE1, ROE2, ROE3 35 I/O exp. board: Relay output statuses
V1.19 DOE1 36 I/O exp. board: Digital output 1 status
V1.20 PID Reference % 20 In percent of the maximum frequency
V1.21 PID Actual value % 21 In percent of the maximum actual value
V1.22 PID Error value % 22 In percent of the maximum error value
V1.23 PID Output % 23 In percent of the maximum output value
V1.24 Autochange outputs 1, 2, 3 30 Used only in pump and fan control
V1.25 Mode 66 Shows the current drive configuration
mode selected with start-up wizard:
0 = No mode selected (Default)
1 = Standard
2 = Fan
3 = Pump
4 = High performance