Parameter List
Table 7-2: Basic Parameters (Control Keypad: Menu P2 ➔ B2.1)
Code Parameter Min. Max. Unit Default Cust. ID Note
P2.1.1 Min. frequency 0.00 Par. 2.1.2 Hz 0.00 101
P2.1.2 Max. frequency Par.
2.1.1
320.00 Hz 50.00 102 NOTE: If f
max
> than the motor
synchronous speed, check
suitability for motor and drive
system
P2.1.3 Acceleration time 1 0.1 3000.0 s 1.0 103
P2.1.4 Deceleration time 1 0.1 3000.0 s 1.0 104
P2.1.5 Current limit 0.1 x I
L
1.5 x I
L
AI
L
107 NOTE: Formulas apply
approximately for drives up to
MF3. For greater sizes, consult
the factory.
P2.1.6
Nominal voltage of
the motor
180 690 V 240V:230V
480V:400V
110
P2.1.7
Nominal frequency
of the motor
30.00 320.00 Hz 50.00 111 Check the rating plate of the
motor
P2.1.8
Nominal speed of
the motor
300 20 000 rpm 1440 112 The default applies for a 4-pole
motor and a nominal size
drive.
P2.1.9
Nominal current of
the motor
0.3 x I
L
1.5 x I
L
AI
L
113 Check the rating plate of the
motor
P2.1.10
Motor cosϕ 0.30 1.00 0.85 120 Check the rating plate of the
motor
P2.1.11
Start function 0 1 0 505 0 = Ramp
1 = Flying start
P2.1.12 Stop function 0 1 0 506 0 = Coasting
1 = Ramp
P2.1.13 V/f optimization 0 1 0 109 0 = Not used
1 = Automatic torque boost
P2.1.14 I/O reference 0 4 0 117 0 = AI1
1 = AI2
2 = Keypad reference
3 = Fieldbus reference
(FBSpeedReference)
4 = Motor potentiometer
P2.1.15 AI2 signal range 1 2 2 390 Not used if AI2 Custom min
>0% or AI2 custom max.
<100%
1 = 0 – 20 mA
2 = 4 – 20 mA
3 = 0 – 10V
4 = 2 – 10V