SM65 Supervisory Module Handbook
10
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
Keypad Access Security
Requires SM65 version 3 or later.
This feature prevents accidental or unauthorized changes to settings from the SM65 keypad.
► To enable Keypad Access Control
1 In DCTools go to Configuration > Communications.
2 Set UI Access to Protected.
3 Click Apply Changes.
4 Now, to make changes to settings from the SM65 keypad first press 7 and 6 together
for more than 10 seconds.
5 To remove Keypad Access Control set UI Access to Unprotected.
About Display Modes
The SM65 menu structure has four display modes:
• Main Display Mode – for viewing system values
• Status View Mode – for viewing system statuses as well as viewing and clearing alarms
• Configuration Mode – for viewing settings of configurable parameters
• Edit Mode – for editing the configurable parameters in Configuration Mode
For easy reference see the supervisory module menu structure on the inside front and back
covers.
Changing display modes
► To enter a display mode
• From Main Display Mode, press : to enter Status View Mode and Alarm Mode.
• From Main Display Mode, press 8 to enter Configuration Mode and Edit Mode.
► To exit a display mode
• Press 9 to return from any mode to Main Display Mode.
Scrolling within a display mode
► To scroll within a display mode
• Press 7 to scroll up within a display mode.
• Press 6 to scroll down within a display mode.
To scroll through a display mode faster, hold down
7
or
6
Using Edit mode
For details about Edit Mode refer to Viewing and Editing Configuration File Parameters on
page
13.