SM65 Supervisory Module Handbook
16
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
► To restart shutdown rectifiers using DCTools
1 Start DCTools (refer to the Communications Options on page
30).
2 From the DCTools System Summary (Home) screen, go to Rectifiers
.
3 Click on the Restart ALL Rectifiers button.
4 Click the Apply Changes button.
Manual Start Equalize
This function starts the Equalize control function (see details on page 52), if conditions allow.
SM65 version 4.04 or later:
If there is an AC supply fail then Equalize will have the state Pending. Equalize will then start
when AC power is restored (unless Fast Charge is enabled then Equalize will start when the
Fast Charge is completed).
Use Reset Battery State to cancel a Pending Equalize. See details on page
17.
Equalize will be active for the configured Duration or until it is stopped manually.
► To manually start Equalize using the SM65 keypad
1 Press: to go to Status View Mode.
2 Press 6 until the display shows Next Equalize ... or Manual Equalize Can Start.
If the display shows Equalize Disabled then Equalize must be Enabled before it can be
started. Go to Configuration Mode to Enable.
3 Press 8 to start Equalize.
4 Equalize will operate for the configured Duration or press 8 to stop Equalize.
► To manually start Equalize using DCTools
1 Start DCTools (refer to the Communications Options on page
30).
2 Go to Voltage Control > Equalize.
3 Click on Start (Equalize must be Enabled).
4 Click Apply Changes.
5 Equalize will operate for the configured Duration or click on Stop then Apply Changes to
stop Equalize.