EasyManua.ls Logo

Eaton SM65 - Page 63

Eaton SM65
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CellSure Status Messages
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
57
Start of Dischge
(String Start of Discharge)
The string is discharging, if the string current exceeds the set threshold.
String SOH Fail
(String State of Health Fail)
A warning that the string may need to be replaced.
String SOH Low
(String State of Health
Low)
The condition of the strings is poor or requires extended float charging or a
boost recharge.
String SOH Poor
(String State of Health
Poor)
An early warning that a string is in poor condition and may need replacing
soon.
Str Abs T High
(String Temp High
Absolute)
The temperature of the pilot cell in a string exceeds the set threshold and
alarm time limits. The string and ambient temperatures should be similar
when the batteries are on float. If the string temperature exceeds the normal
operating temperature of the battery, the battery is being thermally stressed
resulting in reduced life.
Str T High Charg
(String Temp High
Ambient Charge)
The string temperature exceeds the ambient temperature for the set
threshold and alarm time limits. The alarm indicates that the temperature of
the pilot cell in a string has increased significantly. This in turn indicates
thermal run away or overcharged cells.
Str T High Float
(String Temp High
Ambient Float)
The string temperature exceeds the ambient temperature for the set
threshold and alarm time limits. The alarm indicates that the temperature of
the pilot cell in a string has increased significantly. This in turn indicates
thermal run away or overcharged cells.

Table of Contents

Related product manuals