MN04003009E
13
December 2003
STEP 4 (Continued)
Protections — M1 G1.7
Auto Restart Parameters — M1 G1.8
Code Parameter Min. Max. Unit Default Cust ID Note
P1.7.1 Response to
4 mA reference
fault
05 0 700 0 = No response
1 = Warning
2 = Warning+Previous
Freq.
3 = Wrng+Preset Freq
P1.7.2
4 = Fault, stop per
P1.4.7
5 = Fault, stop by
coasting
P1.7.2 4 mA reference
fault frequency
0.00 P1.1.2 Hz 0.00 728
P1.7.3 Response to
external fault
03 2 701 0 = No response
1 = Warning
2 = Fault, stop per
P1.4.7
3 = Fault, stop by
coasting
P1.7.4 Input phase
supervision
03 0 730 See P1.7.3
P1.7.5 Response to
undervoltage fault
13 2 727 See P1.7.3
P1.7.6 Output phase
supervision
03 2 702 See P1.7.3
P1.7.7 Earth fault
protection
03 2 703 See P1.7.3
P1.7.8 Thermal protection
of the motor
03 2 704 See P1.7.3
P1.7.9 Motor ambient
temperature factor
-100.0 100.0 % 0.0 705
P1.7.10 Motor cooling
factor at zero
speed
0.0 150.0 % 40.0 706 As a % of I
nMotor
P1.7.11 Motor thermal
time constant
1 200 min 45 707
P1.7.12 Motor duty cycle 0 100 % 100 708
P1.7.13 Stall protection 0 3 0 709 See P1.7.3
P1.7.14 Stall current 0.1 I
nMotor
x 2
AI
L
710
P1.7.15 Stall time limit 1.00 120.00 s 15.00 711
P1.7.16 Stall frequency
limit
1.0 P1.1.2 Hz 25.0 712
P1.7.17 Underload
protection
03 0 713 See P1.7.13
P1.7.18 Underload protect.
f
nom
torque
10.0 150.0 % 50.0 714
P1.7.19 Underload
protect. f
0
torque
5.0 150.0 % 10.0 715
P1.7.20 Underload
protect. time limit
2.00 600.00 s 20.00 716
P1.7.21 Response to
thermistor fault
03 2 732 See P1.7.3
P1.7.22 Response to
fieldbus fault
03 2 733 See P1.7.3
P1.7.23 Response to slot
fault
03 2 734 See P1.7.3
Code Parameter Min. Max. Unit Default Cust ID Note
P1.8.1 Wait time 0.10 10.00 s 0.50 717
P1.8.2 Trial time 0.00 60.00 s 30.00 718
P1.8.3 Start function 0 2 0 719 0 = Ramp
1 = Flying start per
P1.4.6
2 = System defined
P1.8.4 Number of tries after
undervoltage trip
010 0 720
P1.8.5 Number of tries after
overvoltage trip
010 0 721
P1.8.6 Number of tries after
overcurrent trip
03 0 722
P1.8.7 Number of tries after
reference trip
010 0 723
P1.8.8 Number of tries after
motor temperature
fault trip
010 0 726
P1.8.9 Number of tries after
external fault trip
010 0 725
P1.8.10 Number of tries after
underload fault trip
010 1 738
MN04003009E.fm Page 13 Thursday, February 17, 2005 11:59 AM