22 Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01
Table 7. User Settings (Continued)
Main Menu Screen Submenu Submenu Menu Function
BATT LOW TIME 3 MIN* (Default) [0MIN]
[3MIN] .. [60MIN]
The alarm triggers when the
set battery time remaining is
reached.
COM SETTINGS
REMOTE ON /OFF NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or fault that will
actuate Output signal
parameters through external
contact connector.
REMOTE PWR OFF NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or fault that will
actuate Output signal
parameters through external
contact connector.
INPUT DB9–4
NO* (Default) [NO] [ROO]
[RPO] [BUILDING ALARM]
[FORCED BYPASS] [ON
GENERATOR] [SHUTDOWN
CMD]
Delay time and active cannot
set by LCD.
delay time: 3s
active: open
Sets events or fault that will
actuate Output signal
parameters through external
contact connector or RS232.
OUTPUT RELAY BATTERY FAULT* (Default)
[ON BATTERY] [LOW
BATTERY] [BATTERY FAULT]
[BYPASS] [UPS OK] [LOAD
PROTECTED] [LOAD
POWERED] [GENERAL
ALARM] [BAT CHARGING]
[OVLD PREALARM] [BAT
DISCONN]
Sets events or fault that will
actuate Output signal
parameters through external
contact connector or RS232.
OUTPUT DB9–1 LOW BATTERY* (Default) [ON
BATTERY] [LOW BATTERY]
[BATTERY FAULT] [BYPASS]
[UPS OK] [LOAD PROTECTED]
[LOAD POWERED] [GENERAL
ALARM] [BAT CHARGING]
[OVLD PREALARM] [BAT
DISCONN]
Sets events or fault that will
actuate Output signal
parameters through external
contact connector or RS232.
User Settings