14 Web Config Tool for XC-104-… and XC-204-…
14.1 Logging in to the Web Config Tool
Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com 135
14 Web Config Tool for XC-104-… and XC-204-…
The Web Config Tool can be used to configure
XC-104-… and XC-204-… modular PLCs with operating system version
V3.1.0.0 or higher. Access is possible with an up-to-date browser installed on
a connected device or the PC.
Security
The encryption uses a 2048-bit RSA key. This key will be generated on the
device the first time it starts. Please note that the Web Config Tool cannot be
used at all without this encryption.
Since there is no way to check a certificate in local IP ranges, the "Untrusted
certificate" dialog box will be shown. Instead, you can check whether the cer-
tificate's digital thumbprint has changed so as to prevent man-in-the-middle
attacks.
Remote use
The XControl Web Config Tool can be accessed through a remote browser.
14.1 Logging in to the Web Config Tool
In order to be able to access the Web Config Tool, you must know the IP
address of the device that you want to configure. The device or the PC with
which you want to access the XControl device must be in the same subnet
as the XControl device.
The service runs on port 8375 and uses HTTPS. This means that if the
device's IP address is, for example, "192.168.119.204", the URL will be
"https://192.168.119.204:8375/#/login".
To open the Web Config Tool, follow the steps below.
After logging in, you can use the Web Config Tool as described below.
Password setup
If you reset the device to its factory settings, the Web Config Tool will ask
you to create a password when you access the device. The default language
will be English.
By default, there is no password.
→
Please note that Internet Explorer is not supported.
→
This means that the first person who logs in will be the person
creating the password.