20 Appendix
20.3 Technical specifications
172 Modular PLCs XControl: XC-104-…, XC-204-…, XC-303-… 01/23 MN050005EN Eaton.com
20.3 Technical specifications
20.3.1 General ambient conditions
XC-104-… XC-204-… XC-303-…
Ambient climatic conditions
Standards IEC/EN/DIN EN 61131-2 IEC/EN/DIN EN 611-2 IEC/EN/DIN EN 61131-2
Ambient temperature -20…+60°C
-
20…+55°C
Storage temperature
–25…+70°C –40…+80°C
Mounting position
horizontal and vertical,
relative to the DIN-rail
Derating must be taken into account for vertical
mounting
horizontal,
relative to the DIN-rail
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5…95%
Air pressure (in operation) max. 2000m max. 2000m max. 2000m
Ambient mechanical conditions
Protection Style IEC: IP20
Vibration resistance
constant amplitude (5 - 8.4 Hz ) ±3.5 mm ±3.5 mm ±3.5 mm
Constant acceleration (8.4 - 150 Hz) g
±1.0 ±1.0 ±1.0
Shock resistance half sinewave, 15 g/11 ms 18 impact resistances 18 impact resistances 9 impact resistances
Drop / drop height (IEC EN 60068-2-31) 50 mm 50 mm 50 mm
Free fall, packaged (EN60068-2-32) 0.3m 0.3m 0.3m
Overvoltage category II II II
Pollution degree 2 2 2
Insulation resistance (UL61010-2)
– –
500 V
eff
Connection terminals Plug-in terminal block
Terminal capacities
Spring-cage terminals
solid 0.2 - 1.5mm
2
Flexible with uninsulated ferrule 0.25 - 1.5mm
2
Flexible with insulated ferrule 0.25 - 0.75mm
2
Collar d≤ 2.8mm
AWG 24-16
Strip length 10mm
PLC
Microprocessor PLC NXP CORTEX A7 Single
with 800 MHz + CORTEX
M4 with 200 MHz
NXP CORTEX A7 Dual with
1 GHz + CORTEX M4 with
200 MHz
Freescale CORTEX A7 Dual
core with 960 MHz
Memory
Program memory eMMC-FLASH: 2 GB QSPI-FLASH: 128 MB
Cache memory
DDR3L-RAM: 256 MB DDR-RAM: 512 MB DDR-RAM: 512 MB