16 Digital output module XN-322-12DO-P17
16.4 Technical data for digital outputs
103 XN300 slice modules 02/24 MN050002EN Eaton.com
16.4 Technical data for digital outputs
Quantity 12
Short-circuit proof as per EN 61131-2 Yes
Power supply for digital outputs
Number of supply voltages 3 (clamp positions +1/+2/+3)
Rated operating voltage U
e
24 Vdc
admissible range 18 – 30 VDC
Residual ripple 5%
Maximum permissible total current per power supply group,
with four channels each, when using a duty factor of 100%
3.4A
Maximum permissible total current for all channels when using
a duty factor of 100%
10.2A
Protection against polarity reversal
no
Output characteristic data
„1“ signal
Output voltage (U
e
- 1V) < U
a
< U
e
Max. Output current per channel 1.7 A
„0“ signal
Output voltage < 0.1 VDC
Max. output current per channel 100 A
Switching-on delay < 200 s
Switch off delay < 200 s
Maximum breaking energy of outputs (inductive load) 0.64 Joule/channel
1.95 joules / power supply group