EasyManua.ls Logo

Eaton XN300 - 16.4 Technical data for digital outputs

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Digital output module XN-322-12DO-P17
16.4 Technical data for digital outputs
103 XN300 slice modules 02/24 MN050002EN Eaton.com
16.4 Technical data for digital outputs
Quantity 12
Short-circuit proof as per EN 61131-2 Yes
Power supply for digital outputs
Number of supply voltages 3 (clamp positions +1/+2/+3)
Rated operating voltage U
e
24 Vdc
admissible range 18 30 VDC
Residual ripple 5%
Maximum permissible total current per power supply group,
with four channels each, when using a duty factor of 100%
3.4A
Maximum permissible total current for all channels when using
a duty factor of 100%
10.2A
Protection against polarity reversal
no
Output characteristic data
„1“ signal
Output voltage (U
e
- 1V) < U
a
< U
e
Max. Output current per channel 1.7 A
„0“ signal
Output voltage < 0.1 VDC
Max. output current per channel 100 A
Switching-on delay < 200 s
Switch off delay < 200 s
Maximum breaking energy of outputs (inductive load) 0.64 Joule/channel
1.95 joules / power supply group

Other manuals for Eaton XN300

Related product manuals