20 XN-322-16DIO-PC05 digital input/output module
20.3 Wiring
135 XN300 slice modules 02/24 MN050002EN Eaton.com
20.3.5 Connecting EN 61131-2 short-circuit proof digital outputs
Four digital outputs can be wired to the X3 connector and another four digital
outputs can be wired to the X4 connector. The outputs are able to drive
twice their rated operational current briefly when driving loads with higher
inrush currents.
Large currents may be produced when inductive loads are switched off.
Because of this, digital outputs should be protected with a suppressor circuit.
Figure 82: Example of a suppressor circuit
20.3.6 Wiring example
Figure 83: Wiring example showing how to connect inputs to X1/X2 and outputs to X3/X4
NOTICE
When switching inductive loads, a snubber must be added at
the load in order to prevent EMI.
+ 24 V ⎓
0 V ⎓
Q
X3 X5
(X3/X4)
24V 0V
O1 O3O2 O4 O5 O7O6 O8
F1
X4
X1
I1 I2
I3 I4 I8
X2
I5 I6
I7
PE
24 V
0 V