21 Multi-I/O module XN-322-16MIO-DIOAI
21.4 Technical data
XN300 slice modules 02/24 MN050002EN Eaton.com 144
21.4 Technical data
21.4.1 Voltage measurement analog input
Table 7 Technical data for analog inputs
21.4.2 Filtering:
The low-pass cutoff frequency can be configured for the voltage input
channel by using the appropriate register. This cutoff frequency is specified
in Hz without any decimal places.
The following settings are valid:
Analog inputs 1
Measuring range -10…+10 V 0 V …+10 V
Measured value -30,000…+30,000 0 … +30,000
D-A converter 16 Bit
Resolution min. 0.3 mV / LSB
Conversion time per channel 15.26 s
Common-mode range ± 12 V
Input resistance
normally 660 k
Open wire monitoring Yes
Input filters
Hardware Typically: 1 kHz (third-order low-pass filter)
Software (parameterizable) parameterizable
Measuring accuracy
Cumulative error ± 10V ±0.2% of full scale value
Total potentiometer error ±0.3% of full scale value
Low-pass cut-off frequency Register value
Filter disabled (default) 0x0000
1 Hz
0x0001
10 Hz 0x000A
25 Hz 0x0019
50 Hz 0 x0032
100 Hz 0x0064
250 Hz 0x00FA
500 Hz
0x01F4
1000 Hz 0x03E8