25 Analog input module XN-322-8AI-PTKT
25.6 Filtering:
185 XN300 slice modules 02/24 MN050002EN Eaton.com
25.6 Filtering:
The low-pass cutoff frequency can be configured for each input channel
using the appropriate register. This cutoff frequency is specified in Hz
without any decimal places.
Values from 0 to 100 are allowed.
0: No filter. A value of 1 to 100 corresponds to 1 to 100 Hz
Example: 50 Hz low-pass cutoff frequency; register value: 50
dec
/ 32
hex
The following values are allowed:
Table 10 Configurable low-pass filter.
Low-pass cut-off frequency
Register value
Filter disabled (default) 0x0000
1 Hz 0x0001
10 Hz 0x000A
25 Hz 0x0019
50 Hz
0x0032
100 Hz 0x0064
250 Hz 0x00FA
500 Hz 0x01F4
1000 Hz 0x03E8