26 Analog input module XN-322-10AI-TEKT
26.3 Memory layout
XN300 slice modules 02/24 MN050002EN Eaton.com 198
0x30AD
–
– 2 IntRefInput2
Temperature reading KTY2(i)
The 0x30AD object contains ten times the temperature measured by the
internal KTY2(i) temperature sensor at the cold junction. When internal
temperature compensation is selected, the software will automatically take
into account the value in object 0x30AC.
–
0x4001 – 0x9xx0
SUB 08
max.10 CAN: SerialNumber
EC: Serialnumber
–
0x4004 – 0x8xx1
SUB 01
1 UserLEDControl –
0x400C – –
Max. 25 ProductName –
0x4080 – – 2 FirmwareVersion –
0x50A0 – 0x8xx6
SUB 01
1 SensorTypeSelectChannel1_2 AI1 Bit 0-3 Table 15,
page 199
0x0106
AI2 Bit 4-7
0x50A1 – –
1 SensorTypeSelectChannel3_4 AI3 Bit 0-3 Table 15,
page 199
0x0107
AI4 Bit 4-7
0x50A2 – – 1 SensorTypeSelectChannel5_6 AI5 Bit 0-3 Table 15,
page 199
0x0108
AI6 Bit 4-7
0x50A3 – – 1 SensorTypeSelectChannel7_8 AI7 Bit 0-3 Table 15,
page 199
0x0109
AI8 Bit 4-7
0x50A4 – – 1 ReferenceInputSelect
Used to assign a external cold-
junction compensation
channel
(One of the two KTY sensors is
assigned to analog input AIn
for cold-junction compensa-
tion purposes concerning the
temperature readings)
AI1 Bit 0 0 = KTY 1
1 = KTY 2
0x010A
AI2 Bit 1 0 = KTY 1
1 = KTY 2
AI3 Bit 2 0 = KTY 1
1 = KTY 2
AI4 Bit 3 0 = KTY 1
1 = KTY 2
AI5 Bit 4 0 = KTY 1
1 = KTY 2
AI6 Bit 5 0 = KTY 1
1 = KTY 2
AI7 Bit 6 0 = KTY 1
1 = KTY 2
AI8 Bit 7 0 = KTY 1
1 = KTY 2
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description
Switc
hing
conta
ct
Bit Description Local I/O