EasyManua.ls Logo

Eaton XN300 - Page 203

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 Analog input module XN-322-10AI-TEKT
26.3 Memory layout
199 XN300 slice modules 02/24 MN050002EN Eaton.com
In the registers used to select a sensor, the low nibble (bits 0-3) is used to
configure the lower channel (channel 1, 3, 5, 7), while the high nibble (bits 4-
7) is used to configure the upper channel (channel 2, 4, 6, 8).
Table 15 Sensor selection list
0x50A4
1 ReferenceInputSelectIntExt
Used to select whether
internal or external cold-junc-
tion compensation will be
used for the respective input.
(One of the two KTY sensors is
assigned to analog input AIn
for cold-junction compensa-
tion purposes concerning the
temperature readings)
AI1 Bit 0 0 = KTY external
1 = KTY 1(i)
internal
0x010B
AI2 Bit 1 0 = KTY external
1 = KTY 1(i)
internal
AI3 Bit 2 0 = KTY external
1 = KTY 1(i)
internal
AI4 Bit 3 0 = KTY external
1 = KTY 1(i)
internal
AI5 Bit 4 0 = KTY external
1 = KTY 2 internal
AI6 Bit 5 0 = KTY external
1 = KTY 2(i)
internal
AI7 Bit 6 0 = KTY external
1 = KTY 2(i)
internal
AI8 Bit 7 0 = KTY external
1 = KTY 2(i)
internal
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description
Switc
hing
conta
ct
Bit Description Local I/O
addresses
Hexadecimal value Catalog
Number
Measuring range
Bit 0-3
Bit 4-7
0
hex
J -10 … +690 °C
1
hex
K -40…+940 °C
2
hex
T -40…+400 °C
3
hex
E 0…+520 °C
4
hex
N -80… +1080 °C
5
hex
S -50…+1760 °C
6
hex
R -50… +1760 °C
7
hex
B 0… +1820 °C
8
hex
L 0…+680 °C
9
hex
U 0…+590 °C
A-F
hex
reserved

Other manuals for Eaton XN300