31 XN-322-4AIO-I analog input/output module
31.3 Wiring topic
XN300 slice modules 02/24 MN050002EN Eaton.com 236
31.3 Wiring topic
Two analog inputs can be wired to connector X1. A measuring range of 4 –
20 mA with open wire monitoring is supported, as is a measuring range of 0
– 20 mA without open wire monitoring.
The current input channels use a differential voltage measurement at an
internal module resistor with a resistance of 50 .
It must be ensured that the input signals' voltage levels fall within the
permissible common mode range.
Two analog outputs for a burden resistance of less than 500 can be wired
to connector X2.
0 < R
burden
< 500
Figure 130: Connecting example showing signal current sources at X1 and burden current
sources at X2
X1
1+ 1- 2+ 2-
X2
1+ - 2+ -
X3
PE
24 V
0 V
+
-
+
-
F1
I
max
24V 24V 0V 0V