EasyManua.ls Logo

Eaton XN300 - Page 267

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33 Analog weigh module XN-322-2DMS-WM
33.8 Memory layout
263 XN300 slice modules 02/24 MN050002EN Eaton.com
0x5061 0x8xx6
SUB 02
2 RangeConfigChannel1
Measuring range configuration
for channel 1 (AI1)
Bit 0-2 GAIN 0x0108
0: GAIN 1 ( ± 120mV)
1: reserved
2: reserved
3: GAIN 8 ( ± 15mV) (default)
4: GAIN 16 ( ± 7.5mV)
5: GAIN 32 ( ± 3.75mV)
6: GAIN 64 ( ± 1.875mV)
Bit 3-15 reserved
0x5062 0x8xx6
SUB 03
2 MeasuringConfigChannel2
Measuring configuration for
channel 2 (AI2)
Bit 0-9 Filter depth of ADC 1–1023 (Default
= 2)
0x010A
Bit 10 0: SINC4 filter (Default),
1: SINC3 filter
Bit 11-13 Resize mode
0: Continuous conversion mode
(default)
6: System zero-scale calibration
7: System full-scale calibration
Bit 14, 15 reserved
0x5063 0x8xx6
SUB 04
2 RangeConfigChannel2
Measuring range configuration
for channel 2 (AI2)
Bit 0-2 GAIN 0x010C
0: GAIN 1 ( ± 120mV)
1: reserved
2: reserved
3: GAIN 8 ( ± 15mV) (default)
4: GAIN 16 ( ± 7.5mV)
5: GAIN 32 ( ± 3.75mV)
6: GAIN 64 ( ± 1.875mV)
Bit 3-15 reserved
0x5064
0x8xx6
SUB 05
4 ZeroScaleChannel1 Scale start value for zero point cali-
bration for channel 1
0x010E
0x5065
0x8xx6
SUB 06
4 FullScaleChannel1 Scale end value for zero point cali-
bration for channel 1
0x0112
0x5066
0x8xx6
SUB 07
4 ZeroScaleChannel2 Scale start value for zero point cali-
bration for channel 1
0x0116
0x5067
0x8xx6
SUB 08
4 FullScaleChannel2 Scale end value for zero point cali-
bration for channel 2
0x011A
CAN
Object
Index
Default
CAN
Mapping
EtherCAT
Object
Index
Size
(byte)
Local I/O
description
Local I/O
addresse
s

Other manuals for Eaton XN300

Related product manuals