2 Installation
2.3 Connection terminals
XN300 slice modules 02/24 MN050002EN Eaton.com 24
2.3 Connection terminals
Plug connector
X1 – Xn: The required plug connectors with push-in spring-cage terminals are
included as standard with every XN300 slice module. To use them, the con-
ductor simply needs to be slid into the appropriate contact.
In order to release the conductor, simply press on the release mechanism,
e.g., with a screwdriver, to pull out the conductor from the corresponding
contact.
Table 1 Connection specifications
Table 2 Technical data for plug connectors XN-322-…
Table 3 Technical data for plug connectors XN-322-4DO-RNO
Cable cross-sectional areas
XN-322-… XN-322-4DO-RNO
XN-322-5DO-RCO
10 mm (0.39“) solid mm
2
0.2 – 1.5 0.2 – 2.5
10 mm (0.39“) flexible with
uninsulated ferrule
mm
2
0.2 – 1.5 0.25 – 2.5
10 mm (0.39“) flexible with
insulated ferrule
mm
2
0.2 – 0.75 0.25 – 2.5
Ferrule d mm
2.8 3.8
AWG 24 16 24 12
Strip length mm 10 10
Technical data as per IEC/DIN/VDE Unit solid Flexible Flexible
Insulating material group I
Overvoltage category/pollution degree
–/– III/3 III/2 II/2
Device Voltage Rating V 160 200 400
Rated surge voltage kV 2.5 2.5 2.5
Rated operational current/cross-sectional area
A/mm
2
6/1.5
Technical data as per IEC/DIN/VDE
Unit solid Flex-
ible
Flex-
ible
Insulating material group I
Overvoltage category/pollution degree –/– III/3 III/2 II/2
Device Voltage Rating
V 320 320 630
Rated surge voltage
kV 4 4 4
Rated operational current/cross-sectional area A/mm
2
12/2.5
d ⌀d