EasyManua.ls Logo

Eaton XN300 - Page 322

Eaton XN300
347 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38 XN-322-2SI-RS serial interface specialty module
38.6 Memory layout
XN300 slice modules 02/24 MN050002EN Eaton.com 318
38.6 Memory layout
38.6.1 CANopen objects
For product-specific CANopen or EtherCAT objects please refer
to the manual for the respective gateway
"CANopen Gateway XN-312-GW-CAN", MN050003EN
"EtherCAT Gateway XN-312-GW-EC", MN050010EN.
CAN
Object
Index
Default
CAN
Mapping
Size
(byte)
Local I/O
description
Local I/O
addresses
0x1027 2 CAN: ModuleID Module ID number
0x3200 2 Status232
Setting up the
RS232 interface
via „Modem Status
Register“ and „Line
Status Register“
Byte 0
Modem
Status-
Register
Bit 0 1:Delta Clear to
Send Signal
received
0x0180
Bit 1 1: Delta Data Set
Ready
Bit 2 1: Trailing Edge
Ring Indicator
Bit 3 1: Delta Data
Carrier Detect
Bit 4 1: Clear to Send
Bit 5 1: Data Set Ready
Bit 6 1: Ring Indicator
Bit 7 1: Data Carrier
Detect
Byte 1
Line
Status
Register
Bit 0 1: Transmitter
Holding Register
Empty
Bit 1 1: Rx Parity Error
Bit 2 1: Rx Framing Error
Bit 3 1: Break Condition
receivedBit
Bit 4 1: Tx Busy
Bit 5 1: Receive Buffer
Overflow
Bit 6-7 reserved

Other manuals for Eaton XN300

Related product manuals