5. External connections
5.4 Ethernet 1, Ethernet 2
5.4 Ethernet 1, Ethernet 2
The Ethernet 1 port on the XV300 can be used as a communication interface or as a
real-time field bus interface.
The Ethernet 2 port on the XV300 Touch Panel XV-3.3-..-C..-...-.. can only be used as a
communication interface without real-time requirements.
The Ethernet controllers support transfer rates of 10 Mbit/s and 100 Mbit/s.
When the green LEDlights up, this means that there is a LINK, i.e., that an active net-
work is connected and has been detected.
When the yellow LED flashes, this means that data is being transferred.
Figure 28: RJ-45 socket, 8-pole, 2 LEDs (CAT5e/6), LAN1, 10/100 Mbps
For the network, use shielded twisted-pair (STP) cables only.
For connecting:
The XV300 to a device:
l Use a crossover cable.
The XV300 to a hub/switch:
l Use a patch cable (1:1).
Max. cable length: 100m.
CAUTION
FORCESONTHEETHERNETINTERFACE
Communicationsmaybeaffected,andtheconnection'smechanicalcom-
ponentsmaybedamaged,iftheEthernetinterfaceissubjectedtostrong
vibrationsortheRJ45plug-inconnectionissubjectedtopulling.
l Protect the RJ45 plug-in connection from strong vibrations.
l Protect the RJ45 plug-in connection from tensile forces at the socket.
To commission the communication between the XV300 and the device, follow the
description for the connected device.
XV30012/15 MN048017 ENwww.eaton.eu