5. External connections
5.8 XV300 Touch Panel as a SmartWire-DT® coordinator
Load the PLC project onto the XV300 Touch Panel.
Configuration tests
The configurations are compared every time the power supply is switched on.
l The modules that are actually on the network will be compared with the target con-
figuration stored on the device:
If the SmartWire-DT® network's physical configuration matches the target con-
figuration, the SmartWire-DT® network will be ready to start transferring data.
l The target configuration stored in the device will be compared with the project con-
figuration defined in the PLC:
If the target configuration matches the project configuration, the Config LED will light
up with a solid green light.
SWD-LED
IndicateswhetherthephysicalconfigurationoftheSWDnetworkmatchesthetargetcon-
figurationstoredintheXV300.
Status Description
off
No target configuration present
Redcontinuouslight
• Short-circuit on the 15V DC power supply.
• No SmartWire-DT® module found.
Redflashing
The modules found in the SmartWire-DT® net-
work do not match the target configuration.
A SmartWire-DT® module configured as neces-
sary is missing.
Flashingwithanorange
light
The SmartWire-DT® network's physical con-
figuration is being imported and stored as a new
target configuration in the device.
Greenflashing
• The physical configuration of the SmartWire-
DT® network is compared with the target con-
figuration.
• The SmartWire-DT® modules are addressed.
Greencontinuouslight
• The modules found in the SmartWire-DT® net-
work match the target configuration.
• The SmartWire-DT® network is ready for data
exchange.
Table 24: SWD-LED
XV30012/15 MN048017 ENwww.eaton.eu
63