12. Troubleshooting
Fault Cause Remedy
Engine does not start - Oil pressure switch tripped (red LED
(Fig. 2/Item 8))
- No diesel fuel
- Mechanical switch (Fig. 5/Item A)
set to “STOP”
- Diesel filter blocked
- Air filter dirty
- Diesel filter frozen due to low out
door temperature
- Check oil level, top up with engine
oil
- Top up with diesel fuel
- Set mechanical switch to “RUN”
- Clean or replace the diesel filter
- Clean or replace the air filter
- Proceed as described in the point
entitled “Winter operation”
Generator has too little or no
voltage
- Controller or capacitor defective
- Overcurrent circuit-breaker has
tripped
- Carbon brushes in generator worn
- Contact authorized after-sales
service outlet
- Press the switch and reduce the
consumers
- Contact authorized after-sales
service outlet