Reference Manual
00809-0200-4420, Rev HC
Section 5: Operation and Maintenance
July 2015
Operation and Maintenance
Unmapped parameter read response?: This is the value returned by the Gateway if the
Ethernet/IP master requests a register with no data assigned to it (empty register). It is
recommended this be set to zero fill to prevent errors.
Table 5-3. System Settings>Protocols>EtherNet/IP
Terms Description
Assembly Object Type Ethernet/IP use Static assembly object.
Ethernet/IP TCP Port The TCP Port used to access Ethernet/IP TCP data directly from the Gateway.
Ethernet/IP UDP Ports The UDP Ports used to access Ethernet/IP UDP data directly from the
Gateway.
Incorporate value’s
associated status as
error?
If the HART variable status indicates a critical failure or if there is a loss of
communications, it will be reported through the Ethernet/IP member.
Value reported for
error (floating point)
Chooses what value is reported if the value’s associated status indicates a
critical failure. Only used if the Gateway is using float representation
NaN Not a number is reported if the value’s associated status indicates a critical
failure.
+Inf Positive infinity is reported if the value’s associated status indicates a critical
failure.
-Inf Negative infinity is reported if the value’s associated status indicates a critical
failure.
Other User defined value is reported if the value’s associated status indicates a
critical failure.
Value reported for
error (native integer)
User defined value is reported if the value’s associated status indicates a
critical failure. Only used if the Gateway is using integer representation.