Configuration
January 2017
Configuration
7. Start a new configuration or load a saved configuration from a file.
8. Perform the steps outlined in the “Creating a flow configuration”section.
9. Once the configuration is complete, disconnect MV Engineering Assistant and the USB Fieldbus
Interface. Then, attach the housing cover and tighten so that metal contacts metal to meet
flame-proof/explosion-proof requirements.
2.3.4 Creating a flow configuration
Engineering Assistant 5.5.1 ver. 2 is designed to guide the user through the setup of the flow
configuration for the Rosemount 3051SMV. This information will be used by the Engineering Assistant to
create the flow configuration parameters that can be sent to the transmitter or saved for future use.
1. Select the fluid designation category.
2. Select the fluid type.
3. Select Next.