650594-001 Rev. B 01/24/19 • Page 2 of 52Appleton • 1.800.621.1506 • www.appletonelec.com
Applications/Intended Use
Disconnect the luminaire from the main supply circuit and wait until the battery gets e-energized (Minimum 90 minutes for
IMLG*********H and minimum 180 minutes for IMLG*********E) before opening the xture. Keep tightly closed when in operation.
Marine and wet locations: Apply a corrosion-inhibiting grease, such as petroleum or soap-thickened mineral oils, in 3 lines, spaced
approximately 120 degrees apart, perpendicular to the threads. Tighten all unused close-up plugs to a torque of 3.8 Nm min.
5.5 Nm max.
Non-hazardous locations where severe weather conditions, excessive moisture, dirt, dust, corrosive atmospheres, and
high ambient temperatures are encountered.
Luminaire to be mounted at a minimum of four (4) feet above the ground.
Luminaire is suitable for mounting height less than fteen (15) feet above ground for 90 minute emergency duration.
Luminaire is suitable for mounting height less than twelve (12) feet above ground for 180 minute emergency duration.
Agency Ratings j
Wet Locations
Type 4X
IP66/67
NOTES:
j Refer to product nameplate, located on the exterior of the housing body for details.